Unit designed for two-stage atmospheric gas burners. It manages and monitors burner operations, ensuring safety through flame detection via ionization probes or infrared detectors. The unit features a pre-ignition time of approximately 15 seconds and a safety interval of 5 seconds. It operates on a 220–240V power supply and is compliant with DIN 4788 and EN 298 standards. The controller is protected against undervoltage, preventing automatic restarts in unsafe conditions. It is suitable for use in stationary warm air generators as per DIN 4794